GCS Low Voltage Distribution Cabinet is suitable for the power distribution system of power plant, petroleum, chemical industry, metallurgy, textile, high-rise building and other industries.With high degree of automation, a complete low-voltage power distribution device in the power supply system with three-phase AC frequency of 50 (60) Hz, rated working voltage of 380V (400) V, (600) V and rated current of 4000A or below.
(1) The main structure of the device adopts 8MF type steel, and the structure adopts two structural forms: assembly and partial welding.E=20 ㎜ on the main frame.
(2) The functional rooms of the unit are strictly separated, and the compartments are mainly divided into functional unit room, bus room and cable room. The functions of each unit are relatively independent.
(3) The feeder cabinet and motor control cabinet are equipped with special cable compartment. The connection between the functional unit room and the cable room is realized through the converter or copper row, which not only improves the reliability of the cable, but also greatly facilitates the installation and maintenance of the cables by users.
(4) The cable compartment has two width sizes (240 ㎜ and 440 ㎜) available, depending on the number of cables, cross section and user convenience and requirements for installation and maintenance.
(5) The functional unit auxiliary contact of the unit is 32 pairs of one unit and above, and 20 pairs of 1 / 2 unit, which can meet the needs of the interface between the automatic user and the computer.
(6) Considering the general safety of dry-type transformer and the economy of oil-immersed transformer, the device can easily form a group with dry-type transformer, or easily connect with the low-voltage bus of oil-immersed transformer.
(7)The drawer as the main body, with both the extraction type and fixed type, can be mixed combination, any choice.
Main circuit rated voltage(v) | exchange380(400)、(660) | |
The Auxiliary circuit is rated at a constant voltage(v) | exchange220/380(400)/110/220 | |
rated frequency(Hz) | 50(60) | |
nominal insulation voltage(v) | 660(1000) | |
rated current(A) | horizontal bus | ≤4000 |
Hammer bus(MCC) | 1000 | |
Bus line is rated to withstand the current for a short time(KA/1s) | 50、80 | |
Bus-rated peak tolerance current(KA)/0.1s | 105/175 | |
Power frequency test voltage(V/1min) | main circuit | 2500 |
accessory circuit | 1760 | |
Bus protection grade | three-phase four-wire system | A.B.C.PEN |
Three-phase five-line system | A.B.C.PEN | |
IP30,IP40 |
Copyright © 2022 By SHZ Power